0204
Catalogue No . 04116
Nominal System Voltage (kV) 24
IEC 273 Designation C6 – 160
Arcing Distance (mm) 280
Creepage Distance (mm) 770
Lightning Impulse Withstand Voltage (kV) 160
Power Frequency Withstand Voltage / Wet (kV) 60
Mechanical Failing Load Test Bending (N) 6000
Torsion (N.m) 1500
Weight (kg) 12
image_pdf