0204
Catalogue No . 0477
Nominal System Voltage (kV) 36
IEC 273 Designation C8 – 250
Arcing Distance (mm) 445
Creepage Distance (mm) 1080
Lightning Impulse Withstand Voltage (kV) 250
Power Frequency Withstand Voltage / Wet (kV) 95
Mechanical Failing Load Test Bending (N) 8000
Torsion (N.m) 2500
Weight (kg) 33